Maintenance
[Infrastructure Maintenance] Cooling Maintenance - Heerlen – March 23, 2026

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Heerlen datacenter. The cooling maintenance has been scheduled for March 23, 2026.

Location:

Heerlen, The Netherlands

Schedule:

Start time: March 23, 2026, 07:00 UTC

End time: March 23, 2026, 16:00 UTC

Planned impact: Reduced redundancy (see below for details)

Reason for Maintenance:

We will perform preventive maintenance on the cooling systems to ensure continued reliability and safe operation.

Expected Impact: During the maintenance the cooling units will be maintained one by one. Cooling will remain available, but redundancy will be temporarily reduced while the work is carried out.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Network Maintenance] Switch Software Upgrade - Ashburn - March 30, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Ashburn datacenter. The network maintenance has been scheduled for March 30, 2026.

Location: Ashburn, United States

Schedule: Start time: March 30, 2026, 08:00 UTC End time: March 30, 2026, 10:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to perform required software upgrades. This software upgrade will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced Redundancy: During this maintenance there will be reduced redundancy while one aggregation switch is maintained at a time.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Busbar Replacement - Rotterdam – March 31, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for March 31, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: March 31, 2026, 05:00 UTC End time: March 31, 2026, 16:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to address a faulty busbar. This critical replacement will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced redundancy: No impact expected but there will be no UPS backup. To ensure there is no impact we will run the generators in sync with the grid.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Network Maintenance] Router Software Upgrade - Oslo - April 1, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Oslo datacenter. The network maintenance has been scheduled for April 1, 2026.

Location: Oslo, Norway

Schedule: Start time: April 1, 2026, 04:00 UTC End time: April 1, 2026, 07:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: We will be performing firmware upgrades on our router(s) to improve quality and ensure long-term reliability.

Expected impact: No Impact: No impact is expected for this maintenance, as the traffic will be routed via alternate paths.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

Past Incidents

Sunday 18th, June 2023

US: Ashburn Backbone link between our Ashburn and Atlanta datacenters down

At this moment, we are experiencing problems with: Backbone link between our Ashburn and Atlanta datacenters.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Ashburn and Atlanta datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link has been restored and the maintenance has been completed.

  • This was a result of a emergency maintenance from one of our vendors.

  • Saturday 17th, June 2023

    RO: Bucharest Backbone link between our Bucharest and Milan datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Bucharest and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Bucharest and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Fiber cut has been repaired

  • A fiber fault has been identified

  • Friday 16th, June 2023

    No incidents reported

    Thursday 15th, June 2023

    Backbone link between our Paris and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Paris and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Paris and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Link has been restored.

  • Our third-party vendor is performing maintenance. We will update this status upon completion of this maintenance.

  • DK: Copenhagen Backbone link between our Copenhagen and Stockholm datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Copenhagen and Stockholm datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Copenhagen and Stockholm datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We have received a hands-off from our vendor.

  • Our link has been restored. We are still watching this link as we are waiting to receive a hands-off from our vendor.

  • US: Ashburn Backbone link between our Ashburn and Atlanta datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Atlanta datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Atlanta datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Fiber cut repaired

  • ES: Madrid Backbone link between our Madrid and Milan datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Madrid and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Madrid and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has been restored. Our vendor is hands-off.

  • NL: Amsterdam Backbone link between our Oslo and Amsterdam datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Oslo and Amsterdam datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Oslo and Amsterdam datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor has confirmed that hands are off and service has been restored following planned maintenance-related outage. This issue is resolved.

  • The third-party provider has extended their maintenance. We will update this status once the maintenance has been completed.

  • Wednesday 14th, June 2023

    No incidents reported

    Tuesday 13th, June 2023

    US: Chicago Backbone link between our Chicago and Seattle datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Chicago and Seattle datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Chicago and Seattle datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We have received the hands-off from our vendor.

  • Our link has been restored. We are still waiting for the hands-off from our vendor.

  • A fiber cut has been identified.

  • NO: Oslo Backbone link between our Oslo and Stockholm datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Oslo and Stockholm datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Oslo and Stockholm datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Repairs are complete and hands are off this link. This issue is resolved.

  • Technicians are on site, awaiting hands confirmation that work is complete.

  • Monday 12th, June 2023

    DE: Frankfurt Backbone link between our Warsaw and Frankfurt datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Warsaw and Frankfurt datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Frankfurt datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Related to scheduled maintenance. This issue is resolved.

  • UAE: Fujairah Backbone link between our Dubai and Fujairah datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Dubai and Fujairah datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dubai and Fujairah datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We have received the hands-off from our vendor. Our link has been restored. The repair has been completed.

  • Our link has been restored. We are watching this link until we received a hands-off from our vendor.

  • Sunday 11th, June 2023

    NL: Rotterdam Smartdc Rotterdam - Degraded cooling capacity

    At this moment, we are experiencing problems with: Rotterdam.

    The cause of the incident is currently: cooling strings is down

    We have taken the following actions to resolve the incident: We are currently monitoring the situation.

    Estimated time of repair: Unknown.

    Impact: Due to a difficulty with one of the cooling units, temperatures are fluctuating but still within norms. Colocation customers might see slightly higher temperatures than usual.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The issues have been fixed. No more cooling issues should now be ongoing currently.

  • The supplier will continue to work on the cooling (distribution) pumps. Currently, we experience that the i3d suites measure higher temperatures (suite 19, 20 and 24) highest temperature suite 19 is 27,7 degrees. Suite 20 is 27 degrees and suite 24, 27,5 degrees.

  • Our engineers found a temporary fix by overriding the controls. Temperatures are dropping rapidly at the moment but Suite 19, 20 and 24 are still running a little hot.

  • An extra engineer has been notified and is on their way, ETA is 15-20 minutes.