Maintenance
[Power Maintenance] Powerhouse 2 Breaker Maintenance - Rotterdam – January 29 through February 9, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for January 29, 2026 through February 9, 2026.

Location: Rotterdam, The Netherlands

Schedule:

Date

Time (UTC)

Maintenance Work

January 29, 2026

06:00 - 16:00

The maintenance will be carried out on the generator and transformer breakers. Once the work is completed, there will be reduced redundancy. During transformer breaker maintenance, Powerhouse 1 will operate on generators. During the generator breaker maintenance, there will be reduced redundancy.

February 2 & 3, 2026

06:00 - 16:00

Maintenance will be performed on the UPS1 breakers. While this maintenance is in progress, generators will run in parallel with the power grid to provide continuity in the event of a grid failure, as UPS protection will not be available during this period.

February 4

06:00 - 16:00

Breaker maintenance on UPS2 will take place. Impacted customers will be notified separately..

February 5

06:00 - 16:00

Power impact may occur due to switching activities in the main panels.

February 6 & 9

06:00 - 16:00

Switching activities will take place in the main power distribution board in Powerhouse 1.

Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: Mandatory maintenance to ensure the safety, reliability and correct operation of our main power infrastructure.

Expected impact: Reduced redundancy: During the maintenance window, parts of the power infrastructure will be worked on one at a time which may temporarily reduce redundancy. Power will remain available throughout the maintenance and customers who may be affected will be notified separately.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://www.i3d.net/support/

[Power Maintenance] UPS Replacement - Rotterdam – February 16, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for February 16, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: February 16, 2026, 06:30 UTC End time: February 16, 2026, 15:00 UTC Planned impact: No impact expected (see below for details)

Reason for this maintenance: The maintenance is a battery replacement with UPS1 and UPS2 in Powerhouse 2. The battery string where the work is being preformed on will be switched off and there will be a lower autonomy on the UPS. If needed the UPS will be set to Bypass and we will run the generators parallel to the grid.

Expected impact: No impact: No impact is expected during this work.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Generator Maintenance - Rotterdam – March 3, 2026

Dear Client,

We would like to notify you of upcoming generator maintenance activities that will affect services in our Rotterdam datacenter. The generator maintenance has been scheduled for March 3, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: March 3, 2026, 07:30 UTC End time: March 3, 2026, 10:30 UTC Planned impact: Impact expected (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure of our Rotterdam facility in the event of a power outage, our generators will undergo testing. We will be simulating a real power outage by switching off power to our phase monitoring systems.

Expected impact:

The lighting will briefly blink and there will be a short interruption on B-feed during the switchover to the emergency power. If everything is working correctly we will switch back when possible without extra interruption.

Reduced redundancy: As the generator control systems are switched to maintenance mode during the test run, auxiliary power redundancy is reduced during the maintenance window.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: Support
You can find maintenance updates and the current situation at i3D.net - Status

Past Incidents

Saturday 6th, April 2024

No incidents reported

Friday 5th, April 2024

NL: Amsterdam Backbone link between our Amsterdam and Johannesburg data centers down

At this moment, we are experiencing problems with: Backbone link between our Amsterdam and Johannesburg data centers.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates. At the moment, the line is up and operational. We've experienced a short, 5 minute downtime on this link.

Estimated time of repair: Not applicable.

Impact: Due to the current incident on our backbone link between our Amsterdam and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Maintenance of this BBL has been completed and has remained stable since.

  • GB: London Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Link is up and operational.

  • Thursday 4th, April 2024

    No incidents reported

    Wednesday 3rd, April 2024

    SA: Johannesburg Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This link has been restored.

  • Tuesday 2nd, April 2024

    US: Dallas Backbone link between our Atlanta and Dallas data centers down

    At this moment, we are experiencing problems with: Backbone link between our Atlanta and Dallas data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Atlanta and Dallas data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link has been restored.

  • US: Ashburn Hardware issues in Ashburn

    At this moment we are experiencing problems with: One of our routers in Ashburn is having some interface errors. Redundancy is in place, no expected service impact.

    The cause of the incident is currently: unknown

    We have taken the following actions to resolve the incident: Our team is investigating.

    Estimated time of repair: unavailable

    Impact: none

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The issue has been resolved.

  • Monday 1st, April 2024

    US: Chicago Backbone link between our Chicago and Atlanta data centers down

    At this moment, we are experiencing problems with: Backbone link between our Chicago and Atlanta data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Chicago and Atlanta data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We have received the hands-off from our vendor.

  • Sunday 31st, March 2024

    SA: Johannesburg Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • Saturday 30th, March 2024

    IN: Mumbai Issues in our Mumbai datacenter

    At this moment, we are experiencing problems with: Connectivity in our Mumbai datacenter.

    The cause of the incident is currently: Router connection lose.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding repair/replacement of the switch in question.

    Estimated time of repair: Unknown.

    Impact: minimal impact is expected.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Remote hands has helped us with our investigation and rebooting the server has restored services.

  • CH: Zürich Backbone link between our Milan and Zurich data centers down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Zurich data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Zurich data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor found the faulty Lim card causing the outage and replaced it which resolved the issue.