Stickied Incidents

Tuesday 3rd, March 2026

ONE Control Panel one.i3d.net Portal Outage

Access has been restored on One Portal (one.i3d.net). We apologize for any inconvenience caused by this.

Maintenance
[Emergency Maintenance] CDN Origin Maintenance - Rotterdam - March 5, 2026

Dear Client,

We would like to notify you of upcoming emergency maintenance activities that will affect services in our Rotterdam datacenter. The emergency maintenance has been scheduled for March 5, 2026.

Location: Rotterdam, Netherlands

Schedule: Start time: March 5, 2026, 11:00 UTC End time: March 5 , 2026, 11:30 UTC Planned impact: Impact expected (see below for details)

Reason for this maintenance: Due to a performance degradation observed in CDN downloads this emergency maintenance is required to be carried out. In order to implement the solution, equipment is required to be rebooted which will stop processes for a brief moment.

Expected impact: Full downtime: Full downtime is expected for the duration of the maintenance. During this maintenance it is not possible to upload new files to CDN origins hosted in our Rotterdam datacenter.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Infrastructure Maintenance] Cooling Maintenance - Heerlen – March 23, 2026

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Heerlen datacenter. The cooling maintenance has been scheduled for March 23, 2026.

Location:

Heerlen, The Netherlands

Schedule:

Start time: March 23, 2026, 07:00 UTC

End time: March 23, 2026, 16:00 UTC

Planned impact: Reduced redundancy (see below for details)

Reason for Maintenance:

We will perform preventive maintenance on the cooling systems to ensure continued reliability and safe operation.

Expected Impact: During the maintenance the cooling units will be maintained one by one. Cooling will remain available, but redundancy will be temporarily reduced while the work is carried out.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Power Maintenance] Busbar Replacement - Rotterdam – March 31, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for March 31, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: March 31, 2026, 05:00 UTC End time: March 31, 2026, 16:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to address a faulty busbar. This critical replacement will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced redundancy: No impact expected but there will be no UPS backup. To ensure there is no impact we will run the generators in sync with the grid.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

Past Incidents

Saturday 10th, August 2024

Backbone link between our Bucharest and Milan data centers down

At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest data centers.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Milan and Bucharest data centers, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Fiber was damaged due to bridge construction work. Technicians arrived and repaired the damage which restored all services.

  • Backbone link between our Milan and Madrid data centers down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Madrid data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Madrid data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This was the result of a planed activity that affected the seacom link. We will continue to monitor this until this planned activity is complete.

  • CA: Montreal Backbone link between our Toronto and Montreal data centers down

    At this moment, we are experiencing problems with: Backbone link between our Toronto and Montreal data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Toronto and Montreal data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • There was vandalism that resulted in a fiber cut for this link. Repairs are completed and services has been restored.

  • CA: Toronto Backbone link between our Newark and Toronto data centers down

    At this moment, we are experiencing problems with: Backbone link between our Newark and Toronto data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Newark and Toronto data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor confirmed a major fiber cut where loose power cables caused a hazard. After the hazard was cleared, repairs has gone underway and completed with services being restored.

  • Friday 9th, August 2024

    US: Ashburn Backbone link between our Ashburn and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our vendor performed maintenance on the circuit.

  • US: Atlanta Backbone link between our Ashburn and Atlanta data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Atlanta data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Atlanta data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Maintenance have been completed.

  • This was the result of a maintenance by a third party with our vendor. We will monitor till it is complete.

  • Thursday 8th, August 2024

    NL: Heerlen Backbone link between our Heerlen and Frankfurt data centers down

    At this moment, we are experiencing problems with: Backbone link between our Heerlen and Frankfurt data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Heerlen and Frankfurt data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • There was a cable damage that was done by a third party. Technicians have repaired the damage that was done to the cable and services were restored.

  • Wednesday 7th, August 2024

    SA: Johannesburg Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Services has remained stable for 24 hours and will be setting this as fixed.

  • Services has been restored but haven't received confirmation for a hands off.

  • US: Chicago Backbone link between our Ashburn and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • PL: Warsaw Backbone link between our Warsaw and Moscow data centers down

    At this moment, we are experiencing problems with: Backbone link between our Warsaw and Moscow data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Moscow data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • US: Ashburn Backbone link between our Ashburn and Atlanta data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Atlanta data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Atlanta data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • Tuesday 6th, August 2024

    UA: Kyiv Backbone link between our Kyiv and Bucharest data centers down

    At this moment, we are experiencing problems with: Backbone link between our Kyiv and Bucharest data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Kyiv and Bucharest data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • IT: Milan Backbone link between our Milan and Bucharest data centers down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • Monday 5th, August 2024

    No incidents reported

    Sunday 4th, August 2024

    US: Dallas Outage in Dallas datacenter

    **At this moment we are experiencing problems with: Several devices in our Dallas datacenter

    **The cause of the incident is currently: Under investigation

    **We have taken the following actions to resolve the incident: We contacted the on site team to investigate.

    **Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The remote team has fixed the issues. We will keep monitoring the situation.