Maintenance
[Power Maintenance] UPS Replacement - Rotterdam – February 16, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for February 16, 2026.

Location:

Rotterdam, The Netherlands

Schedule:

Start time: February 16, 2026, 06:30 UTC

End time: February 16, 2026, 15:00 UTC

Planned impact: No impact expected (see below for details)

Reason for this maintenance:

The maintenance is a battery replacement with UPS1 and UPS2 in Powerhouse 2. The battery string where the work is being preformed on will be switched off and there will be a lower autonomy on the UPS. If needed the UPS will be set to Bypass and we will run the generators parallel to the grid.

Expected impact:

No impact is expected during this work.

[Power Maintenance] Generator Maintenance - Rotterdam – March 3, 2026

Dear Client,

We would like to notify you of upcoming generator maintenance activities that will affect services in our Rotterdam datacenter. The generator maintenance has been scheduled for March 3, 2026.

Location:

Rotterdam, The Netherlands

Schedule:

Start time: March 3, 2026, 07:30 UTC

End time: March 3, 2026, 10:30 UTC

Planned impact: Impact expected (see below for details)

Reason for this maintenance:

To ensure the proper functioning of our power infrastructure of our Rotterdam facility in the event of a power outage, our generators will undergo testing. We will be simulating a real power outage by switching off power to our phase monitoring systems.

Expected impact:

The lighting will briefly blink and there will be a short interruption on B-feed during the switchover to the emergency power. If everything is working correctly we will switch back when possible without extra interruption.

Reduced redundancy: As the generator control systems are switched to maintenance mode during the test run, auxiliary power redundancy is reduced during the maintenance window.

Past Incidents

Friday 21st, January 2022

IT: Milan Backbone link between our Milan and Madrid datacenters is down

At this moment we are experiencing problems with: Backbone link between our Milan and Madrid datacenters.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: No ETR available at this time.

Impact: Due to the current incident on our backbone link between our Milan and Madrid datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our vendor has reported they have resolved this issue and we are seeing a return to normal service levels.

  • UAE: Dubai Backbone link between our Dubai and Mumbai datacenters down

    At this moment we are experiencing problems with: Backbone link between our Dubai and Mumbai datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Dubai and Mumbai datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved and the repair works have been completed.

  • Our vendor reported a double fault on the sea cable fiber. Al tough no ETR is reported, due to the location of the fault we do not expect this incident to be fixed on short notice.

  • Thursday 20th, January 2022

    US: Dallas Backbone link between our Dallas and Los Angeles datacenters

    At this moment we are experiencing problems with: Backbone link between our Dallas and Los Angeles datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Dallas and Los Angeles datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Repairs are completing but we have not received a hands-off yet from our vendor.

  • Physical damage to the fiber has been confirmed. Crews have been dispatched and repairs are under way. No ETA at this time.

  • US: Chicago Backbone link between our Dallas and Chicago datacenters down

    At this moment we are experiencing problems with: Backbone link between our Dallas and Chicago datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Dallas and Chicago datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • After an emergency maintenance to repair a damaged fiber by our vendor, this incident has been resolved.

  • Wednesday 19th, January 2022

    No incidents reported

    Tuesday 18th, January 2022

    ES: Madrid Backbone link between our Saint-Denis and Madrid datacenters down

    At this moment we are experiencing problems with: Backbone link between our Saint-Denis and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Saint-Denis and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • The circuit is operational once again, however our vendor is not hands-off yet.

  • IT: Milan Backbone link between our Zurich and Milan datacenters down

    At this moment we are experiencing problems with: Backbone link between our Zurich and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Zurich and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Monday 17th, January 2022

    ES: Madrid Backbone link between our Madrid and Johannesburg datacenters down

    At this moment we are experiencing problems with: Backbone link between our Madrid and Johannesburg datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Madrid and Johannesburg datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The issues have been resolved.

  • We are receiving traffic again. Since we have no official hands-off from our vendor yet, we will monitor the link stability.

  • Sunday 16th, January 2022

    No incidents reported

    Saturday 15th, January 2022

    US: Chicago Backbone link between our Dallas and Chicago datacenters down

    At this moment we are experiencing problems with: Backbone link between our Dallas and Chicago datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Dallas and Chicago datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • DE: Frankfurt Frankfurt DC - Linecard - Outage

    At this moment we are experiencing problems with: Linecard in Frankfurt DC

    The cause of the incident is currently: Known

    We have taken the following actions to resolve the incident: We are investigating and working to restore service.

    Estimated time of repair: None at this time.

    Impact: Users in and through this area may experience congestion.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The linecard has been replaced and all connectivity is back online.

  • Our engineer has arrived. ETR is 21:00 UTC.

  • The linecard will be replaced. ETR is 19:00 UTC.

  • The linecard is back online but we are investigating some of the links remaining down. Not all end-users connecting to our services in or via Frankfurt were impacted, but those that were might have seen slightly increased latency.

  • Friday 14th, January 2022

    NL: Amsterdam Backbone link between our Amsterdam and Copenhagen datacenters down

    At this moment we are experiencing problems with: Backbone link between our Amsterdam and Copenhagen datacenters.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and have reached out to our vendor for investigation.

    Estimated time of repair: Unknown

    Impact: Due to the current ongoing incident on our backbone link between our Amsterdam and Copenhagen datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • DE: Frankfurt Backbone link between our Frankfurt and Warsaw datacenters down

    At this moment we are experiencing problems with: Backbone link between our Frankfurt and Warsaw datacenters

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and have reached out to our vendor for investigation.

    Estimated time of repair: Unknown

    Impact: Due to the current ongoing incident on our backbone link between our Frankfurt and Warsaw datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • The fault has been located. Groundworks caused a fiber cut and the expected ETR is set to 21:00 UTC