Some systems are experiencing issues

About This Site

Welcome to the status page of i3D.net. Any known issues affecting any of our services will be tracked on this page. Potential impact may vary from customer to customer depending on the systems or services impacted.

All times used on this page will be in the UTC timezone.

You can subscribe to receive an email as soon as a status update has been published. You may consult our Privacy Statement for more information on the processing of your personal data.

Please reach out to our support team through our website or support@i3d.net if you have any questions or need help.

We are also available 24/7 by phone on the following phone numbers:

+31 (0)10 890 00 70

1-800-482-6910

Maintenance
[Power Maintenance] UPS Replacement - Rotterdam – February 16, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for February 16, 2026.

Location:

Rotterdam, The Netherlands

Schedule:

Start time: February 16, 2026, 06:30 UTC

End time: February 16, 2026, 15:00 UTC

Planned impact: No impact expected (see below for details)

Reason for this maintenance:

The maintenance is a battery replacement with UPS1 and UPS2 in Powerhouse 2. The battery string where the work is being preformed on will be switched off and there will be a lower autonomy on the UPS. If needed the UPS will be set to Bypass and we will run the generators parallel to the grid.

Expected impact:

No impact is expected during this work.

[Power Maintenance] Generator Maintenance - Rotterdam – March 3, 2026

Dear Client,

We would like to notify you of upcoming generator maintenance activities that will affect services in our Rotterdam datacenter. The generator maintenance has been scheduled for March 3, 2026.

Location:

Rotterdam, The Netherlands

Schedule:

Start time: March 3, 2026, 07:30 UTC

End time: March 3, 2026, 10:30 UTC

Planned impact: Impact expected (see below for details)

Reason for this maintenance:

To ensure the proper functioning of our power infrastructure of our Rotterdam facility in the event of a power outage, our generators will undergo testing. We will be simulating a real power outage by switching off power to our phase monitoring systems.

Expected impact:

The lighting will briefly blink and there will be a short interruption on B-feed during the switchover to the emergency power. If everything is working correctly we will switch back when possible without extra interruption.

Reduced redundancy: As the generator control systems are switched to maintenance mode during the test run, auxiliary power redundancy is reduced during the maintenance window.

Past Incidents

Saturday 10th, September 2022

US: Ashburn Backbone link between our Ashburn and Newark datacenters down

At this moment, we are experiencing problems with: Backbone link between our Ashburn and Newark datacenters.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Ashburn and Newark datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved by our vendor.

  • SA: Johannesburg Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We confirmed the link to be online and passing traffic.

  • Friday 9th, September 2022

    FR: Paris Backbone link between our Paris and Madrid datacenters down

    At this moment we are experiencing problems with: Backbone link between our Paris and Madrid datacenters.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Paris and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link was restored. Vendor started maintenance early. Keeping an eye on the link

  • RO: Bucharest Backbone link between our Milan and Bucharest datacenters down

    At this moment we are experiencing problems with: Backbone link between our Milan and Bucharest datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Thursday 8th, September 2022

    DE: Frankfurt Backbone link between our Heerlen and Frankfurt datacenters down

    At this moment we are experiencing problems with: Backbone link between our Heerlen and Frankfurt datacenters down.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Heerlen and Frankfurt datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • SA: Johannesburg Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • The link has been stable for over 6 hours. This issue is resolved.

  • Link is restored. Awaiting hands-off from vendor

  • ES: Madrid Backbone link between our Madrid and Milan datacenters

    At this moment we are experiencing problems with: Backbone link between our Madrid and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Madrid and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Backbone link between our Moscow and Hong Kong datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Moscow and Hong Kong datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Moscow and Hong Kong datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link is stable.

  • The link has stabilized. The engineer is still working on the repair.

  • An engineer is on site working on the faulty module.

  • ES: Madrid Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The Link status has been confirmed to be online.

  • Wednesday 7th, September 2022

    NL: Rotterdam Smartdc Rotterdam - Degraded cooling capacity

    At this moment we are experiencing problems with: Degraded cooling capacity in our Rotterdam datacenter.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently investigating the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to degraded cooling capacity, temperatures are rising. Colocation customers will see higher temperatures than usual.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The chiller has been fixed and vendor is hands off. Temperatures where kept within normal levels during this maintenance.

  • One of chillers is still experiencing issues. We will continue to investigate.

  • PL: Warsaw Backbone link between our Warsaw and Moscow datacenters down

    At this moment we are experiencing problems with: Backbone link between our Warsaw and Moscow datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Moscow datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor has completed the emergency maintenance successfully and is hands of. Services are restored resolving this incident.

  • This incident was caused by a emergency maintenance from our vendor. At this time the link is restored and we are awaiting vendor hands off.

  • Tuesday 6th, September 2022

    HK: Hong Kong Backbone link between our Santa Clara and Hong Kong datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Santa Clara and Hong Kong datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Santa Clara and Hong Kong datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link is up, and we received confirmation.

  • Monday 5th, September 2022

    NL: Rotterdam Smartdc Rotterdam - Degraded cooling capacity

    At this moment we are experiencing problems with: Degraded cooling capacity in our Rotterdam datacenter.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently investigating the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to degraded cooling capacity, temperatures are rising. Colocation customers will see higher temperatures than usual.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The component has been fixed and the maintenance has concluded.

  • Our vendor indicates the situation will remain stable during the night with the current bypass of a faulty component. An emergency maintenance will start at 04:00 UTC to replace said component.

  • An additional engineer from our vendor has arrived.

  • Sunday 4th, September 2022

    No incidents reported