Maintenance
[Cooling Maintenance] Cooling Maintenance - Rotterdam – June 22, 2026

Dear Client,

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Rotterdam datacenter. The cooling maintenance has been scheduled for June 22, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: June 22, 2026, 05:00 UTC End time: July 10, 2026, 14:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: We will be performing a cooling maintenance on our cooling units to continue reliability and stability.

Expected impact:

Reduced redundancy: No impact expected, but there will be reduced redundancy during the maintenance window. There maybe some small temperature fluctuations as the units are being worked on.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Network Maintenance] Switch Software Upgrade - Rotterdam - June 24, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Rotterdam datacenter. The network maintenance has been scheduled for June 24, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: June 24, 2026, 03:00 UTC End time: June 24, 2026, 06:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required in preparation for an upgrade to a new switch firmware. This will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced redundancy: No impact expected, but there will be reduced redundancy during the maintenance window.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Generator Maintenance - Heerlen – July 3, 2026

Dear Client,

We would like to notify you of upcoming generator maintenance activities that will affect services in our Heerlen datacenter. The generator maintenance has been scheduled for July 3, 2026.

Location: Heerlen, The Netherlands

Schedule: Start time: July 3, 2026, 05:00 UTC End time: July 3, 2026, 14:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure, our generators will undergo a power load test. This is only an inspection and no power outages are planned for this activity.

Expected impact: No Impact: No impact is expected for this maintenance, as there is no outage for the power systems.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/
You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Yearly Generator Maintenance - Rotterdam – July 7, 2026

We would like to notify you of upcoming backup generator maintenance activities. This maintenance will not affect services in our Rotterdam datacenter. The maintenance has been scheduled for July 7 until July 17, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: July 7, 2026, 05:00 UTC End time: July 17, 2026, 14:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure, our backup generators will undergo preventative maintenance.

Expected impact: No Impact: No impact is expected for this maintenance, as regular power systems will not be touched. Customers in the datacenter at the time of the maintenance could hear loud noises.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

Past Incidents

Sunday 11th, September 2022

No incidents reported

Saturday 10th, September 2022

US: Ashburn Backbone link between our Ashburn and Newark datacenters down

At this moment, we are experiencing problems with: Backbone link between our Ashburn and Newark datacenters.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Ashburn and Newark datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved by our vendor.

  • SA: Johannesburg Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We confirmed the link to be online and passing traffic.

  • Friday 9th, September 2022

    FR: Paris Backbone link between our Paris and Madrid datacenters down

    At this moment we are experiencing problems with: Backbone link between our Paris and Madrid datacenters.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Paris and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link was restored. Vendor started maintenance early. Keeping an eye on the link

  • RO: Bucharest Backbone link between our Milan and Bucharest datacenters down

    At this moment we are experiencing problems with: Backbone link between our Milan and Bucharest datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Thursday 8th, September 2022

    DE: Frankfurt Backbone link between our Heerlen and Frankfurt datacenters down

    At this moment we are experiencing problems with: Backbone link between our Heerlen and Frankfurt datacenters down.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Heerlen and Frankfurt datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • SA: Johannesburg Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • The link has been stable for over 6 hours. This issue is resolved.

  • Link is restored. Awaiting hands-off from vendor

  • ES: Madrid Backbone link between our Madrid and Milan datacenters

    At this moment we are experiencing problems with: Backbone link between our Madrid and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Madrid and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Backbone link between our Moscow and Hong Kong datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Moscow and Hong Kong datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Moscow and Hong Kong datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link is stable.

  • The link has stabilized. The engineer is still working on the repair.

  • An engineer is on site working on the faulty module.

  • ES: Madrid Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The Link status has been confirmed to be online.

  • Wednesday 7th, September 2022

    NL: Rotterdam Smartdc Rotterdam - Degraded cooling capacity

    At this moment we are experiencing problems with: Degraded cooling capacity in our Rotterdam datacenter.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently investigating the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to degraded cooling capacity, temperatures are rising. Colocation customers will see higher temperatures than usual.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The chiller has been fixed and vendor is hands off. Temperatures where kept within normal levels during this maintenance.

  • One of chillers is still experiencing issues. We will continue to investigate.

  • PL: Warsaw Backbone link between our Warsaw and Moscow datacenters down

    At this moment we are experiencing problems with: Backbone link between our Warsaw and Moscow datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Moscow datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor has completed the emergency maintenance successfully and is hands of. Services are restored resolving this incident.

  • This incident was caused by a emergency maintenance from our vendor. At this time the link is restored and we are awaiting vendor hands off.

  • Tuesday 6th, September 2022

    HK: Hong Kong Backbone link between our Santa Clara and Hong Kong datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Santa Clara and Hong Kong datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Santa Clara and Hong Kong datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link is up, and we received confirmation.

  • Monday 5th, September 2022

    NL: Rotterdam Smartdc Rotterdam - Degraded cooling capacity

    At this moment we are experiencing problems with: Degraded cooling capacity in our Rotterdam datacenter.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently investigating the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to degraded cooling capacity, temperatures are rising. Colocation customers will see higher temperatures than usual.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The component has been fixed and the maintenance has concluded.

  • Our vendor indicates the situation will remain stable during the night with the current bypass of a faulty component. An emergency maintenance will start at 04:00 UTC to replace said component.

  • An additional engineer from our vendor has arrived.