Maintenance
[Power Maintenance] Busbar Replacement - Rotterdam – March 31, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for March 31, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: March 31, 2026, 05:00 UTC End time: March 31, 2026, 16:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to address a faulty busbar. This critical replacement will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced redundancy: No impact expected but there will be no UPS backup. To ensure there is no impact we will run the generators in sync with the grid.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Network Maintenance] Router Software Upgrade - Oslo - April 1, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Oslo datacenter. The network maintenance has been scheduled for April 1, 2026.

Location: Oslo, Norway

Schedule: Start time: April 1, 2026, 04:00 UTC End time: April 1, 2026, 07:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: We will be performing firmware upgrades on our router(s) to improve quality and ensure long-term reliability.

Expected impact: No Impact: No impact is expected for this maintenance, as the traffic will be routed via alternate paths.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Infrastructure Maintenance] Load Balancer and Database update - Global - April 22, 2026

Dear Client,

We would like to notify you of upcoming infrastructure maintenance activities that will affect services globally. The maintenance has been scheduled for April 22, 2026.

Location: Global

Schedule: Start time: April 22, 2026, 10:00 UTC End time: April 22, 2026, 11:00 UTC Planned impact: Impact expected (see below for details)

Reason for this maintenance: We will be performing updates on our database to improve quality and ensure long-term reliability.

Expected impact: Service degradation: During the maintenance all users will be disconnected while the switchover is performed. Calls to the API will briefly fail during the switchover.

Affected services: ONE portal: users will be logged out Smartdc portal: users will be logged out ODP: hostagents connection will be reset API: during the switchover calls will fail

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Power Maintenance] Breaker Maintenance Powerhouse 1 - Rotterdam – April 29

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for April 29, 2026

Location: Rotterdam, The Netherlands Suite 2 A Feed Suite 19 A and A+ Feed Suite 34 A and A+ Feed

Schedule: Start time: April 29, 2026, 08:00 UTC End time: April 29, 2026, 12:00 UTC Planned impact: Impact expected (see below for details)

Reason for this maintenance: Mandatory maintenance to ensure the safety, reliability and correct operation of our main power infrastructure.

Expected impact: Reduced redundancy: During the maintenance window, one of the power feeds supplying Suite 2, 19 and 34 will be temporarily unavailable. Power will remain available through the remaining feed(s), but power redundancy will be reduced for approximately 4 hours.

Please note that devices with a single power supply (single PSU) or devices connected only to the A feed will experience a service interruption during this maintenance window. Devices with dual power supplies connected to separate feeds are expected to remain online.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: i3d.net/support

[Cooling Maintenance] Water Cooling Pump Maintenance - Rotterdam – May 4, 2026

Dear Client,

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Rotterdam datacenter. The water cooling pump maintenance has been scheduled for May 4, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: May 4, 2026, 07:00 UTC End time: May 4, 2026, 15:30 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: Our vendor will be performing a maintenance on the water pumps in our Rotterdam datacenter.

Expected impact: No Impact: No impact is expected, as maintenance activities will be performed on each water pump individually, with the team waiting for each pump to return to operation before proceeding to the next.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Generator On-load Test - Rotterdam – May 5, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for May 5, 2026

Location: Rotterdam, The Netherlands

Original window: Start time: May 5, 2026, 06:00 UTC End time: May 5, 2026, 09:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure, our generators will undergo an on-load test run.

Expected impact: No Impact: No impact is expected for this maintenance, as there is no outage for the power systems. Customers in the datacenter at the time of the maintenance can hear loud noises.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

Past Incidents

Wednesday 16th, November 2022

CA: Montreal Backbone link between our Montreal and Amsterdam datacenters

At this moment we are experiencing problems with: Backbone link between our Montreal and Amsterdam datacenters.

The cause of the incident is currently: unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: unknown

Impact: Due to the current incident on our backbone link between our Montreal and Amsterdam datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Backbone link between our Hong Kong and Moscow datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Hong Kong and Moscow datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Hong Kong and Moscow datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has restored.

  • Tuesday 15th, November 2022

    US: Chicago Backbone link between our Chicago and Santa Clara datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Chicago and Santa Clara datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Chicago and Santa Clara datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Our link has been restored. Waiting to receive a hands-off from our vendor.

  • Our provider has sent the following update: The damage was located on a 360-count fiber cable on railroad property. Therefore, railroad personnel has been engaged. Some repair crews are onsite and on standby, and another crew is in route transporting new cable to the fault site.

  • NL: Amsterdam Backbone link between our Amsterdam and Oslo datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Amsterdam and Oslo datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Amsterdam and Oslo datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The tech has replaced the damaged section. The line is back online, stable for over 9 hours.

  • There was a damaged section in the cable, it has been replaced by the technician. The line is back online, however we are still waiting for a hands-off.

  • FR: Paris Backbone link between our Frankfurt and Warsaw datacenters down

    At this moment we are experiencing problems with: Backbone link between our Germany and Warsaw datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Germany and Warsaw datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has been restored.

  • Our link went down right after the maintenance was completed. We are communicating with our vendor and will update you accrdingly.

  • Vendor maintenance is being performed. Estimated End Time: 15.11.2022 05:00 GMT

  • Monday 14th, November 2022

    No incidents reported

    Sunday 13th, November 2022

    SA: Johannesburg Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This was due to a planned vendor maintenance between 07:00 - 10:00 UTC.

  • Saturday 12th, November 2022

    No incidents reported

    Friday 11th, November 2022

    UAE: Fujairah Backbone link between our Dubai and Fujairah datacenters is down

    At this moment we are experiencing problems with: Backbone link between our Dubai and Fujairah datacenters.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We have reached out to our vendor for more information.

    Estimated time of repair: No ETR at this time.

    Impact: Due to the current incident on our backbone link between our Dubai and Fujairah datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has been restored.

  • Maintenance is being performed set to complete ETA 9 AM UTC

  • IT: Milan Backbone link between our Milan and Bucharest datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest datacenters.

    The cause of the incident is currently: A fiber break occurred

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved

  • NL: Amsterdam Backbone link between our Amsterdam and Oslo datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Amsterdam and Oslo datacenters.

    The cause of the incident is currently: We are experiencing intermittent outages

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Amsterdam and Oslo datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This link has been stable and strong for +8 hours. Awaiting RFO.

  • ES: Madrid Backbone link between our Madrid and Milan datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Madrid and Milan datacenters.

    The cause of the incident is currently: there is an network outage on the providers network

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Madrid and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Fiber has been repaired and incident is resolved.

  • This incident is caused by an fiber cut. Repair crews are on-site and working on repairing the damaged fibers at this time. No ETR is known yet.

  • Thursday 10th, November 2022

    NL: Amsterdam Backbone link between our Amsterdam and Oslo datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Amsterdam and Oslo datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Amsterdam and Oslo datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • NL: Amsterdam Backbone link between our Amsterdam and Rotterdam datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Amsterdam and Rotterdam datacenters.

    The cause of the incident is currently: There was a fiber crossing after the maintenance

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Amsterdam and Rotterdam datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Update from the Vendor: Due to a fiber crossing, the connection did not come up after maintenance.

    Due to de-crossing, the connection came back online.

  • Wednesday 9th, November 2022

    US: Dallas Backbone link between our Dallas and Atlanta datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Dallas and Atlanta datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dallas and Atlanta datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link is restored and has been stable for 2 hours

  • A fiber cut has been located and a team is currently working on the repair.

  • RO: Bucharest Backbone link between our Milan and Bucharest datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has been restored and remained stable. We have received a hands-off from our vendor.

  • Latest Update-

    Remote optical measurements by the Colt transmission device suggesting a fibre break at about 52 Kms from Osijek (towards Nasice, Croatia).

    An incident has been raised with the partner to further investigate the issue. We will keep you updated on the progress of incident resolution. Thank you.

  • US: Dallas Backbone link between our Chicago and Dallas datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Chicago and Dallas datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Chicago and Dallas datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This issue has been resolved.

  • A fiber cut has been located and a team is currently working on the repair.

  • US: Seattle Backbone link between our Seattle and Chicago datacenters down

    At this moment we are experiencing problems with: Backbone link between our Seattle and Chicago datacenters.

    The cause of the incident is currently: a possible service interruption

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: ETR is unknown.

    Impact: Due to the current incident on our backbone link between our Seattle and Chicago datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has restored. We are waiting to receive word from our vendor.

  • US: Los Angeles Backbone link between our Santa Clara and Los Angeles datacenters down

    At this moment we are experiencing problems with: Backbone link between our Santa Clara and Los Angeles datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: No ETR available at this time.

    Impact: Due to the current incident on our backbone link between our Santa Clara and Los Angeles datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    UAE: Fujairah Backbone link between our Dubai and Fujairah datacenters is down

    At this moment we are experiencing problems with: Backbone link between our Dubai and Fujairah datacenters.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We have reached out to our vendor for more information.

    Estimated time of repair: No ETR at this time.

    Impact: Due to the current incident on our backbone link between our Dubai and Fujairah datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    US: Santa Clara Backbone link between our Hong Kong and Santa Clara datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Hong Kong and Santa Clara datacenters.

    The cause of the incident is currently: The Fault is due to Repeater Fault

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our 1 and 2 datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We received hands-off from the Vendor.

  • Please be informed that we observed a major outage between Hong Kong & Japan via EAC Segment AC at 21:39 UTC 6 November 2022 affecting your unprotected circuit where service will remain down until fault is permanently fixed. Our support team is investigating the issue on priority and our management and operation teams informed.

    With regards to the ongoing outage, equipment vendor has been engaged to assist investigation. Both Hong Kong and Japan Field Services team have been involved along with Marine team for joint isolation. COTDR measurement has been completed, and we have shared the measurement result with the Marine team for further analysis. The Fault is due to Repeater Fault (RC009) located 466km away from Hongkong Landing Station. Marine Team is focus to get the Faulty Repeater repaired first at the soonest possible time and working with the Maintenance Provider for permitting application/processing and Cableship mobilization.

  • At this moment, we are experiencing problems with: Backbone link between our Hong Kong and Santa Clara datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Hong Kong and Santa Clara datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.