Some systems are experiencing issues

About This Site

Welcome to the status page of i3D.net. Any known issues affecting any of our services will be tracked on this page. Potential impact may vary from customer to customer depending on the systems or services impacted.

All times used on this page will be in the UTC timezone.

You can subscribe to receive an email as soon as a status update has been published. You may consult our Privacy Statement for more information on the processing of your personal data.

Please reach out to our support team through our website or support@i3d.net if you have any questions or need help.

We are also available 24/7 by phone on the following phone numbers:

+31 (0)10 890 00 70

1-800-482-6910

Maintenance
[Power Maintenance] Powerhouse 2 Breaker Maintenance - Rotterdam – January 29 through February 9, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for January 29, 2026 through February 9, 2026.

Location: Rotterdam, The Netherlands

Schedule:

Date

Time (UTC)

Maintenance Work

January 29, 2026

06:00 - 16:00

The maintenance will be carried out on the generator and transformer breakers. Once the work is completed, there will be reduced redundancy. During transformer breaker maintenance, Powerhouse 1 will operate on generators. During the generator breaker maintenance, there will be reduced redundancy.

February 2 & 3, 2026

06:00 - 16:00

Maintenance will be performed on the UPS1 breakers. While this maintenance is in progress, generators will run in parallel with the power grid to provide continuity in the event of a grid failure, as UPS protection will not be available during this period.

February 4

06:00 - 16:00

Breaker maintenance on UPS2 will take place. Impacted customers will be notified separately..

February 5

06:00 - 16:00

Power impact may occur due to switching activities in the main panels.

February 6 & 9

06:00 - 16:00

Switching activities will take place in the main power distribution board in Powerhouse 1.

Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: Mandatory maintenance to ensure the safety, reliability and correct operation of our main power infrastructure.

Expected impact: Reduced redundancy: During the maintenance window, parts of the power infrastructure will be worked on one at a time which may temporarily reduce redundancy. Power will remain available throughout the maintenance and customers who may be affected will be notified separately.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://www.i3d.net/support/

[Power Maintenance] UPS Replacement - Rotterdam – February 16, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for February 16, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: February 16, 2026, 06:30 UTC End time: February 16, 2026, 15:00 UTC Planned impact: No impact expected (see below for details)

Reason for this maintenance: The maintenance is a battery replacement with UPS1 and UPS2 in Powerhouse 2. The battery string where the work is being preformed on will be switched off and there will be a lower autonomy on the UPS. If needed the UPS will be set to Bypass and we will run the generators parallel to the grid.

Expected impact: No impact: No impact is expected during this work.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

Past Incidents

Thursday 24th, November 2022

No incidents reported

Wednesday 23rd, November 2022

RO: Bucharest Backbone link between our Bucharest and Kyiv datacenters down

At this moment, we are experiencing problems with: Backbone link between our Bucharest and Kyiv datacenters.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Bucharest and Kyiv datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has remained stable.

  • Our link has been restored. We are waiting to receive the hands-off from our vendor.

  • Tuesday 22nd, November 2022

    RO: Bucharest Backbone link between our Milan and Bucharest datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our vendor is hands-off. The link has remained stable.

  • The link has remained stable. We are waiting to receive an update from our vendor.

  • Monday 21st, November 2022

    UAE: Dubai Backbone link between our Dubai and Milan datacenters down

    At this moment we are experiencing problems with: Backbone link between our Dubai and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dubai and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link has been restored.

  • A subsea fault has been found.

  • US: Ashburn Backbone link between our Ashburn and St. Denis datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and St. Denis datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and St. Denis datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident was caused by a power failure. The link is restored and stable for several hours resolving this incident.

  • Sunday 20th, November 2022

    No incidents reported

    Saturday 19th, November 2022

    No incidents reported

    Friday 18th, November 2022

    RO: Bucharest Backbone link between our Milan and Bucharest datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our vendor identified a fiber cut. The cut was repaired and our link was restored.

  • Thursday 17th, November 2022

    CA: Montreal Backbone link between our Montreal and Amsterdam datacenters

    At this moment we are experiencing problems with: Backbone link between our Montreal and Amsterdam datacenters.

    The cause of the incident is currently: unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: unknown

    Impact: Due to the current incident on our backbone link between our Montreal and Amsterdam datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link has remained stable. Our vendor is hands-off

  • We are seeing that the circuit is back up. We awaiting information from our vendor for the cause of the incident.

  • SA: Johannesburg Backbone link between our Johannesburg and Madrid datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and Madrid datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and Madrid datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link remain stable and the vendor is hands-off.

  • We are seeing that the circuit is back up. We awaiting information from our vendor for the cause of the incident.

  • US: Seattle Backbone link between our Seattle and Chicago datacenters down

    At this moment we are experiencing problems with: Backbone link between our Seattle and Chicago datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Seattle and Chicago datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our link has remained stable. Our vendor is hands-off.

  • Circuit is restored, but as we received no updates from vendor we keep monitoring this link closely.

  • RO: Bucharest Backbone link between our Bucharest and Budapest datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Bucharest and Budapest datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Bucharest and Budapest datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • There was damage on the optical cable. Repair work is completed; no further interruptions are expected.

  • IT: Milan Backbone link between our Dubai and Milan datacenters down

    At this moment we are experiencing problems with: Backbone link between our Dubai and Milan datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dubai and Milan datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • our vendor is hands-off. our link remained stable.

  • The link has remained stable. We are waiting to receive a hands-off from our vendor.