Maintenance
[Power Maintenance] UPS Replacement - Rotterdam – February 16, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for February 16, 2026.

Location:

Rotterdam, The Netherlands

Schedule:

Start time: February 16, 2026, 06:30 UTC

End time: February 16, 2026, 15:00 UTC

Planned impact: No impact expected (see below for details)

Reason for this maintenance:

The maintenance is a battery replacement with UPS1 and UPS2 in Powerhouse 2. The battery string where the work is being preformed on will be switched off and there will be a lower autonomy on the UPS. If needed the UPS will be set to Bypass and we will run the generators parallel to the grid.

Expected impact:

No impact is expected during this work.

[Power Maintenance] Generator Maintenance - Rotterdam – March 3, 2026

Dear Client,

We would like to notify you of upcoming generator maintenance activities that will affect services in our Rotterdam datacenter. The generator maintenance has been scheduled for March 3, 2026.

Location:

Rotterdam, The Netherlands

Schedule:

Start time: March 3, 2026, 07:30 UTC

End time: March 3, 2026, 10:30 UTC

Planned impact: Impact expected (see below for details)

Reason for this maintenance:

To ensure the proper functioning of our power infrastructure of our Rotterdam facility in the event of a power outage, our generators will undergo testing. We will be simulating a real power outage by switching off power to our phase monitoring systems.

Expected impact:

The lighting will briefly blink and there will be a short interruption on B-feed during the switchover to the emergency power. If everything is working correctly we will switch back when possible without extra interruption.

Reduced redundancy: As the generator control systems are switched to maintenance mode during the test run, auxiliary power redundancy is reduced during the maintenance window.

Past Incidents

Saturday 16th, March 2024

HU: Budapest Backbone link between our Bucharest and Budapest data centers down

At this moment, we are experiencing problems with: Backbone link between our Bucharest and Budapest data centers.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Bucharest and Budapest data centers, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Services has been restored and kept stable since.

  • Friday 15th, March 2024

    SA: Johannesburg Backbone link between our Johannesburg and London data centers down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and London data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and London data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • Our link has been restored, We are still monitoring this link.

  • US: Santa Clara Backbone link between our Santa Clara and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Santa Clara and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Santa Clara and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Our vendor has identified a fiber cut. A team has been dispatched and is working on a repair.

  • Thursday 14th, March 2024

    IN: Mumbai Backbone link between our Mumbai and Singapore data centers down

    At this moment, we are experiencing problems with: Backbone link between our Mumbai and Singapore data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Mumbai and Singapore data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This link has been restored and remained stable.

  • SA: Johannesburg Backbone link between our Madrid and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our Madrid and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Madrid and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This link has remained stable. No further interruptions are expected.

  • We are seeing some traffic restored on the link. We are waiting for another update from our vendor on the status of the repairs.

  • According to WACS NOC, cable ship Sovereign is mobilized for repair operations. Repair is estimated tentatively between 18 – 28 Apr.

  • Repair ship has arrived as of April 8th and works have begun on to repair the SAT-3 cable (one of four major cables.) Two of the remaining cables (ACE and WACS) are expected to be restored on April 17th and April 28th, respectively. The fourth cable (MainOne) is projected to be the final cable to be repaired by May 9th.

  • Check out this article for more details. https://www.theguardian.com/technology/2024/mar/14/much-of-west-and-central-africa-without-internet-after-undersea-cable-failures

  • Our link is down related to a subsea cable fault. No ETR as of yet.

  • Wednesday 13th, March 2024

    HK: Hong Kong Backbone link between our Hong Kong and Tokyo data centers down

    At this moment, we are experiencing problems with: Backbone link between our Hong Kong and Tokyo data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Hong Kong and Tokyo data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We received the hands-off from our vendor.

  • Our link has been restored. We are still monitoring this link as we wait for an update from our vendor.

  • Tuesday 12th, March 2024

    Backbone link between our Chicago and Ashburn data centers down

    At this moment, we are experiencing problems with: Backbone link between our Chicago and Ashburn data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Chicago and Ashburn data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The link has been restored.

  • Monday 11th, March 2024

    PL: Warsaw Backbone link between our Frankfurt and Warsaw data centers down

    At this moment, we are experiencing problems with: Backbone link between our Frankfurt and Warsaw data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Frankfurt and Warsaw data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The issues have been resolved

  • NL: Rotterdam ONE platform is having issues

    At this moment, we are experiencing problems with: ONE Platform is performing issues. The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on. our platform in Rotterdam, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    Sunday 10th, March 2024

    DE: Frankfurt Backbone link between our Paris and Frankfurt data centers down

    At this moment, we are experiencing problems with: Backbone link between our Paris and Frankfurt data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Paris and Frankfurt data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Card was replaced and it has resolved the issue.

  • Vendor confirmed there is a failed AMP card that has caused this issue and working on getting a replacement.

  • Vendor is aware of the outage after the maintenance was completed and is currently investigating the fault.