Some systems are experiencing issues

About This Site

Welcome to the status page of i3D.net. Any known issues affecting any of our services will be tracked on this page. Potential impact may vary from customer to customer depending on the systems or services impacted.

All times used on this page will be in the UTC timezone.

You can subscribe to receive an email as soon as a status update has been published. You may consult our Privacy Statement for more information on the processing of your personal data.

Please reach out to our support team through our website or support@i3d.net if you have any questions or need help.

We are also available 24/7 by phone on the following phone numbers:

+31 (0)10 890 00 70

1-800-482-6910

Maintenance
[Infrastructure Maintenance] Cooling Maintenance - Heerlen – March 23, 2026

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Heerlen datacenter. The cooling maintenance has been scheduled for March 23, 2026.

Location:

Heerlen, The Netherlands

Schedule:

Start time: March 23, 2026, 07:00 UTC

End time: March 23, 2026, 16:00 UTC

Planned impact: Reduced redundancy (see below for details)

Reason for Maintenance:

We will perform preventive maintenance on the cooling systems to ensure continued reliability and safe operation.

Expected Impact: During the maintenance the cooling units will be maintained one by one. Cooling will remain available, but redundancy will be temporarily reduced while the work is carried out.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Network Maintenance] Switch Software Upgrade - Ashburn - March 30, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Ashburn datacenter. The network maintenance has been scheduled for March 30, 2026.

Location: Ashburn, United States

Schedule: Start time: March 30, 2026, 08:00 UTC End time: March 30, 2026, 10:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to perform required software upgrades. This software upgrade will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced Redundancy: During this maintenance there will be reduced redundancy while one aggregation switch is maintained at a time.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Busbar Replacement - Rotterdam – March 31, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for March 31, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: March 31, 2026, 05:00 UTC End time: March 31, 2026, 16:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to address a faulty busbar. This critical replacement will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced redundancy: No impact expected but there will be no UPS backup. To ensure there is no impact we will run the generators in sync with the grid.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Network Maintenance] Router Software Upgrade - Oslo - April 1, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Oslo datacenter. The network maintenance has been scheduled for April 1, 2026.

Location: Oslo, Norway

Schedule: Start time: April 1, 2026, 04:00 UTC End time: April 1, 2026, 07:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: We will be performing firmware upgrades on our router(s) to improve quality and ensure long-term reliability.

Expected impact: No Impact: No impact is expected for this maintenance, as the traffic will be routed via alternate paths.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

Past Incidents

Thursday 8th, August 2024

NL: Heerlen Backbone link between our Heerlen and Frankfurt data centers down

At this moment, we are experiencing problems with: Backbone link between our Heerlen and Frankfurt data centers.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Heerlen and Frankfurt data centers, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • There was a cable damage that was done by a third party. Technicians have repaired the damage that was done to the cable and services were restored.

  • Wednesday 7th, August 2024

    SA: Johannesburg Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Services has remained stable for 24 hours and will be setting this as fixed.

  • Services has been restored but haven't received confirmation for a hands off.

  • US: Chicago Backbone link between our Ashburn and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • PL: Warsaw Backbone link between our Warsaw and Moscow data centers down

    At this moment, we are experiencing problems with: Backbone link between our Warsaw and Moscow data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Moscow data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • US: Ashburn Backbone link between our Ashburn and Atlanta data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Atlanta data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Atlanta data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • Tuesday 6th, August 2024

    UA: Kyiv Backbone link between our Kyiv and Bucharest data centers down

    At this moment, we are experiencing problems with: Backbone link between our Kyiv and Bucharest data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Kyiv and Bucharest data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • IT: Milan Backbone link between our Milan and Bucharest data centers down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Bucharest data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Bucharest data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • Monday 5th, August 2024

    No incidents reported

    Sunday 4th, August 2024

    US: Dallas Outage in Dallas datacenter

    **At this moment we are experiencing problems with: Several devices in our Dallas datacenter

    **The cause of the incident is currently: Under investigation

    **We have taken the following actions to resolve the incident: We contacted the on site team to investigate.

    **Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The remote team has fixed the issues. We will keep monitoring the situation.

  • Saturday 3rd, August 2024

    No incidents reported

    Friday 2nd, August 2024

    UAE: Fujairah Backbone link between our Dubai and Fujairah data centers down

    At this moment, we are experiencing problems with: Backbone link between our Dubai and Fujairah data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dubai and Fujairah data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Maintenance is complete and services has remained stable.

  • This is the result of a maintenance, we will keep watch of this link.

  • Thursday 1st, August 2024

    Backbone link between our Dallas and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Dallas and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dallas and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.