Maintenance
[Cooling Maintenance] Cooling Maintenance Update - Rotterdam – June 22, 2026

Dear Client,

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Rotterdam datacenter. The cooling maintenance has been scheduled for June 22, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: June 22, 2026, 05:00 UTC End time: July 10, 2026, 14:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: We will be performing a cooling maintenance on our cooling units to continue reliability and stability.

Expected impact:

Reduced redundancy: No impact expected, but there will be reduced redundancy during the maintenance window. There maybe some small temperature fluctuations as the units are being worked on.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

Update to original maintenance window:

We would like to notify you of an update to the cooling maintenance activities regarding services in our Rotterdam datacenter originally scheduled for June 22, 2026. There has been an extension on this maintenance window with new dates provided below. The extended maintenance will now be in three stages.

Schedule: Stage 1 Start time: July 28, 2026, 05:00 UTC End time: July 29, 2026, 14:00 UTC

Stage 2 Start time: August 7, 2026, 05:00 UTC End time: August 7, 2026, 14:00 UTC

Stage 3 Start time: August 10, 2026, 05:00 UTC End time: August 13, 2026, 14:00 UTC

Expected impact remains the same.

[Power Maintenance] Generator Maintenance - Heerlen – July 3, 2026

Dear Client,

We would like to notify you of upcoming generator maintenance activities that will affect services in our Heerlen datacenter. The generator maintenance has been scheduled for July 3, 2026.

Location: Heerlen, The Netherlands

Schedule: Start time: July 3, 2026, 05:00 UTC End time: July 3, 2026, 14:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure, our generators will undergo a power load test. This is only an inspection and no power outages are planned for this activity.

Expected impact: No Impact: No impact is expected for this maintenance, as there is no outage for the power systems.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/
You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Yearly Generator Maintenance - Rotterdam – July 7, 2026

We would like to notify you of upcoming backup generator maintenance activities. This maintenance will not affect services in our Rotterdam datacenter. The maintenance has been scheduled for July 7 until July 17, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: July 7, 2026, 05:00 UTC End time: July 17, 2026, 14:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure, our backup generators will undergo preventative maintenance.

Expected impact: No Impact: No impact is expected for this maintenance, as regular power systems will not be touched. Customers in the datacenter at the time of the maintenance could hear loud noises.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

Past Incidents

Tuesday 10th, December 2024

US: Ashburn Backbone link between our Atlanta and Ashburn data centers down

At this moment, we are experiencing problems with: Backbone link between our Atlanta and Ashburn data centers.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Atlanta and Ashburn data centers, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved

  • Monday 9th, December 2024

    Backbone link between our Atlanta and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Atlanta and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Atlanta and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Outage was caused by a maintenance.

  • The line is back up, waiting for RFO from vendor

  • Backbone link between our Bucharest and Milan data centers down

    At this moment, we are experiencing problems with: Backbone link between our Bucharest and Milan data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Bucharest and Milan data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our network partner estimates that the restoration work on the ground fill be finished around 01:00 UTC 11/12

  • A new incident has occured for this link but localized in a different country. The fault location and damage have been identified, due to excavation work the fiber cable was cut. An excavator has arrived on the scene and has started digging work. Two new fiber optic cables will have to be installed to repair the impacted fiber section.

  • This incident is resolved.

  • Phone support Phone support problems

    At this moment we are experiencing problems with: Phone Support

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: Our vendor is investigating this incident.

    Estimated time of repair: No estimated time of repair.

    Impact: Support via phone is unavailable. The Rivium office doorbell and parking barriers cannot be opened remotely.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    GB: London Backbone link between our London and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • At this moment, we are experiencing problems with: Backbone link between our London and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our London and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Sunday 8th, December 2024

    No incidents reported

    Saturday 7th, December 2024

    UAE: Dubai Backbone link between our Dubai and Milan data centers down

    At this moment, we are experiencing problems with: Backbone link between our Dubai and Milan data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Dubai and Milan data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • There was a power feed issue due to isolation of another country. After the switch based on voltage shift, this has been resolved.

  • Friday 6th, December 2024

    No incidents reported

    Thursday 5th, December 2024

    GB: London Backbone link between our Paris and London datacenters down

    At this moment, we are experiencing problems with: Backbone link between our Paris and London datacenters.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Paris and London datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Fiber cut has been repaired by our vendor. No further outages are expected.

  • CA: Montreal Backbone link between our Montreal and Toronto data centers down

    At this moment, we are experiencing problems with: Backbone link between our Montreal and Toronto data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Montreal and Toronto data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • US: Newark Backbone link between our Ashburn and Newark data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Newark data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Newark data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    Wednesday 4th, December 2024

    Backbone link between our Johannesburg and London data centers down

    At this moment, we are experiencing problems with: Backbone link between our Johannesburg and London data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Johannesburg and London data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.