Maintenance
[Cooling Maintenance] Rotterdam – Data Center Air Supply Temperature Change – July 21, 2025

We would like to inform you of an upcoming cooling maintenance being performed in our Rotterdam datacenter. This maintenance is scheduled for July 22nd, 2025.

Location:

Rotterdam, The Netherlands

Schedule:

Start Time: July 21, 2025, 06:00 UTC

End Time: August 21, 2025, 18:00 UTC

Planned downtime:

No downtime is expected

Reason for this maintenance:

As part of our ongoing commitment to energy efficiency and environmental responsibility we will begin increasing the air supply temperature in our server rooms from 22°C to 24°C. This adjustment is being made to improve the overall energy efficiency of our facility, to ensure we continue complying with European regulatory guidelines and to reduce the load on our cooling systems.

Expected downtime/impact:

No downtime is expected.

[Maintenance] 2025 Rotterdam Q3 quarterly on-load tests

Dear customer,

In the below overview you will find the date and time of our planned on-load tests in our  Smartdc Rotterdam datacenter for Q3 2025:

Location: Rotterdam, The Netherlands

On-load test Q3: Startdatum: 5 August 2025, 06:00 UTC Einddatum: 5 August 2025, 08:00 UTC

Expected downtime: None expected

Impact:  No impact expected

Reason for these maintenances: These on-load tests are routine and meant to test the back-up power systems of our Rotterdam facility. This is to ensure that everything remains fully operational in the event of a power outage in the facility.

Support: Our support department will be open during the maintenances. More details about how you can contact our support can be found on https://i3d.net/support/

Past Incidents

Thursday 19th, September 2024

US: Ashburn Backbone link between our Ashburn and Newark data centers down

At this moment, we are experiencing problems with: Backbone link between our Ashburn and Newark data centers.

The cause of the incident is currently: Unknown

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: Unknown.

Impact: Due to the current incident on our backbone link between our Ashburn and Newark data centers, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The issue was confirmed of a bent jumper that affected services. After replacing the jumper. services were restored and we confirmed on our end.

  • Services has returned back but we have not been given the hands off from the technician yet. Will continue to monitor.

  • An outage has been discovered and a technician has been dispatched to the outage for further investigations.

  • Backbone link between our Madrid and Paris data centers down

    At this moment, we are experiencing problems with: Backbone link between our Madrid and Paris data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Madrid and Paris data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Technicians discovered there was a Fiber cut caused by a traffic accident and teams are now working on repairing the cut.

  • CH: Zürich Backbone link between our Frankfurt and Zurich data centers down

    At this moment, we are experiencing problems with: Backbone link between our Frankfurt and Zurich data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Frankfurt and Zurich data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    US: Los Angeles Backbone link between our Los Angeles and Dallas data centers down

    At this moment, we are experiencing problems with: Backbone link between our Los Angeles and Dallas data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Los Angeles and Dallas data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    Wednesday 18th, September 2024

    US: Chicago Backbone link between our Atlanta and Chicago data centers down

    At this moment, we are experiencing problems with: Backbone link between our Atlanta and Chicago data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Atlanta and Chicago data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • It appears to be a fiber cut to be the cause of the issue. Technician has arrived to the site and beginning to troubleshoot to fix the issue.

  • SA: Johannesburg Backbone link between our Madrid and Johannesburg data centers down

    At this moment, we are experiencing problems with: Backbone link between our Madrid and Johannesburg data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Madrid and Johannesburg data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • Tuesday 17th, September 2024

    US: Chicago Backbone link between our Chicago and San Jose data centers down

    At this moment, we are experiencing problems with: Backbone link between our Chicago and San Jose data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Chicago and San Jose data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    Backbone link between our Tokyo and Singapore data centers down

    At this moment, we are experiencing problems with: Backbone link between our Tokyo and Singapore data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Tokyo and Singapore data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

    Monday 16th, September 2024

    Backbone link between our Warsaw and Moscow data centers down

    At this moment, we are experiencing problems with: Backbone link between our Warsaw and Moscow data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Moscow data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor confirmed the presence of a fiber cut. We are observing gradual restauration.

  • Sunday 15th, September 2024

    No incidents reported

    Saturday 14th, September 2024

    ES: Madrid Backbone link between our Milan and Madrid data centers down

    At this moment, we are experiencing problems with: Backbone link between our Milan and Madrid data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Milan and Madrid data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Vendor confirmed that the issue was caused by breaker switch. Technicians will remain on site for the next 2 hours to monitor the situation.

  • PL: Warsaw Backbone link between our Warsaw and Moscow data centers down

    At this moment, we are experiencing problems with: Backbone link between our Warsaw and Moscow data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Warsaw and Moscow data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • A partial cable fault has been repaired by our Service Provider.

  • Friday 13th, September 2024

    RO: Bucharest Backbone link between our Kyiv and Bucharest data centers down

    At this moment, we are experiencing problems with: Backbone link between our Kyiv and Bucharest data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Kyiv and Bucharest data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This was the result of a fiber cut and the issue has been resolved.

  • Thursday 12th, September 2024

    US: Ashburn Backbone link between our Ashburn and Atlanta data centers down

    At this moment, we are experiencing problems with: Backbone link between our Ashburn and Atlanta data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Ashburn and Atlanta data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident is resolved.

  • PL: Warsaw Backbone link between our Frankfurt and Warsaw data centers down

    At this moment, we are experiencing problems with: Backbone link between our Frankfurt and Warsaw data centers.

    The cause of the incident is currently: Unknown

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

    Estimated time of repair: Unknown.

    Impact: Due to the current incident on our backbone link between our Frankfurt and Warsaw data centers, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our vendor has implemented a temporary fix but is not hands-off yet. We will continue to monitor for further updates.