Maintenance
[Power Maintenance] Busbar Replacement - Rotterdam – March 31, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for March 31, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: March 31, 2026, 05:00 UTC End time: March 31, 2026, 16:00 UTC Planned impact: Reduced redundancy (see below for details)

Reason for this maintenance: The maintenance is required to address a faulty busbar. This critical replacement will enhance system reliability and ensure consistent performance moving forward.

Expected impact: Reduced redundancy: No impact expected but there will be no UPS backup. To ensure there is no impact we will run the generators in sync with the grid.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Network Maintenance] Router Software Upgrade - Oslo - April 1, 2026

Dear Client,

We would like to notify you of upcoming network maintenance activities that will affect services in our Oslo datacenter. The network maintenance has been scheduled for April 1, 2026.

Location: Oslo, Norway

Schedule: Start time: April 1, 2026, 04:00 UTC End time: April 1, 2026, 07:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: We will be performing firmware upgrades on our router(s) to improve quality and ensure long-term reliability.

Expected impact: No Impact: No impact is expected for this maintenance, as the traffic will be routed via alternate paths.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[GLAD Maintenance] GLAD Backend Migration - April 20, 2026

Dear Client,

We would like to notify you of upcoming GLAD maintenance activities that will affect services with GLAD. The GLAD maintenance has been scheduled for April 20, 2026.

Schedule: Start time: April 20, 2026, 09:00 UTC End time: April 20, 2026, 14:00 UTC Planned impact: Degradation (see below for details)

Reason for this maintenance: We will be migrating and upgrading our GLAD and Warden backend. This migration is part of our ongoing effort to enhance performance, scalability, and long-term reliability. Migrations and upgrades will be carried subsequently to minimise degradation in service and ensure a seamless transition.

Expected impact: Degradation: Our GLAD API and Warden Armor service will be temporarily unavailable while migrating.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Infrastructure Maintenance] Load Balancer and Database update - Global - April 22, 2026

Dear Client,

We would like to notify you of upcoming infrastructure maintenance activities that will affect services globally. The maintenance has been scheduled for April 22, 2026.

Location: Global

Schedule: Start time: April 22, 2026, 10:00 UTC End time: April 22, 2026, 11:00 UTC Planned impact: Impact expected (see below for details)

Reason for this maintenance: We will be performing updates on our database to improve quality and ensure long-term reliability.

Expected impact: Service degradation: During the maintenance all users will be disconnected while the switchover is performed. Calls to the API will briefly fail during the switchover.

Affected services: ONE portal: users will be logged out Smartdc portal: users will be logged out ODP: hostagents connection will be reset API: during the switchover calls will fail

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

[Power Maintenance] Breaker Maintenance Powerhouse 1 - Rotterdam – April 29

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for April 29, 2026

Location: Rotterdam, The Netherlands Suite 2 A Feed Suite 19 A and A+ Feed Suite 34 A and A+ Feed

Schedule: Start time: April 29, 2026, 08:00 UTC End time: April 29, 2026, 12:00 UTC Planned impact: Impact expected (see below for details)

Reason for this maintenance: Mandatory maintenance to ensure the safety, reliability and correct operation of our main power infrastructure.

Expected impact: Reduced redundancy: During the maintenance window, one of the power feeds supplying Suite 2, 19 and 34 will be temporarily unavailable. Power will remain available through the remaining feed(s), but power redundancy will be reduced for approximately 4 hours.

Please note that devices with a single power supply (single PSU) or devices connected only to the A feed will experience a service interruption during this maintenance window. Devices with dual power supplies connected to separate feeds are expected to remain online.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: i3d.net/support

[Cooling Maintenance] Water Cooling Pump Maintenance - Rotterdam – May 4, 2026

Dear Client,

We would like to notify you of upcoming cooling maintenance activities that will affect services in our Rotterdam datacenter. The water cooling pump maintenance has been scheduled for May 4, 2026.

Location: Rotterdam, The Netherlands

Schedule: Start time: May 4, 2026, 07:00 UTC End time: May 4, 2026, 15:30 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: Our vendor will be performing a maintenance on the water pumps in our Rotterdam datacenter.

Expected impact: No Impact: No impact is expected, as maintenance activities will be performed on each water pump individually, with the team waiting for each pump to return to operation before proceeding to the next.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/ You can find maintenance updates and the current situation at https://status.i3d.net/

[Power Maintenance] Generator On-load Test - Rotterdam – May 5, 2026

Dear Client,

We would like to notify you of upcoming power maintenance activities that will affect services in our Rotterdam datacenter. The power maintenance has been scheduled for May 5, 2026

Location: Rotterdam, The Netherlands

Original window: Start time: May 5, 2026, 06:00 UTC End time: May 5, 2026, 09:00 UTC Planned impact: No impact (see below for details)

Reason for this maintenance: To ensure the proper functioning of our power infrastructure, our generators will undergo an on-load test run.

Expected impact: No Impact: No impact is expected for this maintenance, as there is no outage for the power systems. Customers in the datacenter at the time of the maintenance can hear loud noises.

Support: Our support department will be open during the maintenance. More details about how you can contact our support can be found here: https://i3d.net/support/

Past Incidents

Wednesday 16th, December 2020

DK: Copenhagen Backbone link between our Copenhagen and Moscow datacenters down

At this moment we are experiencing problems with: Backbone link between our Copenhagen and Moscow datacenters down.

The cause of the incident is currently: Our vendor reports a cable was damaged during excavation by local construction crews.

We have taken the following actions to resolve the incident: We are currently monitoring the situation and are in touch with our vendor regarding status updates.

Estimated time of repair: No ETR available at this time.

Impact: Due to the current incident on our backbone link between our Copenhagen and Moscow datacenters, users between these and surrounding regions may experience increased latency.

Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has now been resolved.

  • During final stage of works on repairing this cable, the cable closure was damaged resulting in a second interruption. The current ETR on restoration of the cable closure is 30 minutes.

  • Tuesday 15th, December 2020

    DK: Copenhagen Backbone link between our Copenhagen and Amsterdam datacenters

    At this moment we are experiencing problems with: Backbone link between our Copenhagen and Amsterdam datacenters

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and have reached out to our vendor for investigation.

    Estimated time of repair: Not available at this time.

    Impact: Due to the current ongoing incident on our backbone link between our Copenhagen and Amsterdam datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • The connection is restored and traffic is normalized.

  • Current ETR is reported to be Dec 16, 04:00 UTC.

  • Our vendor reports that field engineers found a fiber optic cut caused by a third-party drilling operation. An emergency team is already on-site and is currently excavating to restore the damaged area. More investigation will need to be done before an ETR can be provided.

  • API v3 i3D.net API unavailable

    At this moment we are experiencing problems with: the i3D.net and Smartdc API, resulting in one.i3d.net also being offline.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently investigating the root cause of this incident which became visible after the switch upgrade this morning (06:00 UTC).

    Estimated time of repair: Not available at this time.

    Impact: Due to the API being unavailable, all API calls as well as one.i3d.net are currently offline. The ONE Deployment Platform cannot be used for new calls, but existing capacity is unaffected.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • We are now fully closing this incident.

  • The API has been stabilized. We will continue monitoring the situation before closing this incident.

  • Monday 14th, December 2020

    Backbone link between our Kyiv and Moscow datacenters

    At this moment we are experiencing problems with: Backbone link between our Kyiv and Moscow datacenters

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and have reached out to our vendor for investigation.

    Estimated time of repair: Not available at this time.

    Impact: Due to the current ongoing incident on our backbone link between our Kyiv and Moscow datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • Our services have restored after they were switched to different optical fibers.

  • Our vendor has informed us that a fire in a cable collector has caused this incident. Their engineers are currently trying to switch services to other optical fibers. There is no ETR / ETA at this moment.

  • Sunday 13th, December 2020

    No incidents reported

    Saturday 12th, December 2020

    No incidents reported

    Friday 11th, December 2020

    No incidents reported

    Thursday 10th, December 2020

    US: Chicago Backbone link between our Chicago and Seattle datacenters

    At this moment we are experiencing problems with: Backbone link between our Chicago and Seattle datacenters

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We are currently monitoring the situation and have reached out to our vendor for investigation.

    Estimated time of repair: Not available at this time.

    Impact: Due to the current ongoing incident on our backbone link between our Chicago and Dallas datacenters, users between these and surrounding regions may experience increased latency.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This incident has been resolved.

  • NL: Rotterdam Incident Ziggo/KPN network

    We are getting reports from customers having trouble connecting to our Rotterdam and Heerlen datacenters. These issues stem from an incident that occurs to start in the Ziggo and/or KPN network. The i3D.net/Smartdc networks are stable so as soon as this third-party incident has been resolved, all connectivity to our datacenter will also be back to normal.

  • It looks like Ziggo customers are no longer experiencing issues, but we do still see complaints coming in for KPN customers.

  • Wednesday 9th, December 2020

    UAE: Dubai Dubai DC - Switch down

    At this moment we are experiencing problems with: One of our switches has gone down.

    The cause of the incident is currently: Unknown.

    We have taken the following actions to resolve the incident: We have reached out to our vendor for investigation.

    Estimated time of repair: Unknown.

    Impact: Customers on that switch will experience an interruption in service.

    Support: Our support department is available for more information and personal updates. New updates will be posted here. More details about how you can contact our support can be found here.

    Subscribe for the latest updates. You may consult our Privacy Statement for more information on the processing of your personal data.

  • This issue has been resolved.

  • Our vendor is working on resolving the incident after identifying the issue with the switch